Calibration gas should be used to calibrate ammonia gas detectors that utilize electrochemical sensor technology as the detection method. It is recommended to calibrate at the same concentration that the main 'high' alarm set point is set to. For example, if the high alarm is set to 100 ppm, it is recommended to calibrate using 100 ppm calibration gas.
Estimate roughly 20 calibrations per bottle, assuming cap is not left off of the bottle for any period long then required to complete the calibration process
This type of gas cannot be used to calibrate solid state sensor technology