Hansen Techni-Level level transducer probes have fast become the industry standard for liquid refrigerant level control and monitoring. These reliable, well engineered electronic level transducer probes, when properly used, operate trouble-free and are not affected by reasonable changes in refrigerant temperature or pressure. They provide a computer compatible 4-20 mA (milliamp) output signal proportional to liquid level. Probes consist of a compact, electronic transmitter in a watertight housing assembled on top of a rugged, capacitance type level sensor. Probe active lengths up to 168" (427 mm) are available. Normally, the probe must be inside a level column. Typical applications include: vertical and horizontal vessels, pump accumulators, pilot receivers, and refrigerant loss monitoring. These probes are operating control devices and should never be used as safety devices.
Note: WLT is a direct replacement for all VLT models.
The WLT-C is used to directly control an MCV without the need for a controller.
More Information
More Information
Weight
30.000000
Condition
New
Manufacturer
Hansen
Enclosure
Watertight NEMA 4
Fitting
3/4" NPT male, connection to Level Column
Maximum Load Resistance
1200 ohms
Safe Working Pressure
400 psig (27 bar)
Standard Active Probe Lengths
20" (510 mm), 30" (760 mm), 40" (1015 mm), 60" (1525 mm), 80" (2030 mm), 100" (2540 mm), 120" (3050 mm), 144" (3660 mm), 168" (4270 mm); Custom lengths available up to 168" (4270 mm) max
Operating Temperature
Transmitter:-20 °F to +140 °F ambient
(-30 °C to +60 °C) ambient
Sensor:-60 °F to +150 °F (-50 °C to +65 °C)
Below-60 °F (-50 °C) requires the stainless
steel extended neck body; contact the factory.