Danfoss ICAD 600A and 1200A Actuator types are dedicated for use with ICM motor-operated valves. There are only two sizes of ICAD actuators that cover the range of valves from ICM 20 to ICM 150.
The Danfoss ICAD is controlled via a modulating analogue signal (e.g. 4 – 20 mA / 2 – 10 V) or a digital ON /OFF signal. ICAD incorporates an advanced MMI (Man Machine Interface), including continuous display of Opening Degree, which gives the user a very advanced and flexible setup procedure that can meet many different applications.
Features:
Designed for industrial refrigeration installations.
Advanced and high-speed Digital Stepper Motor Technology
Seven segment LCD display and three programming keys included
Valve opening degree can be observed continuously.
Can easily be configured to different applications on-site (change speed, ON / OFF, Fail-Safe operation, modulating valve, etc..)
Open – Close time: 3 – 45 seconds depending on valve size
Modulating, ON / OFF operation or Neutral zone / 3 point control
Multiple speed selection during operation
Logging of old alarms
Password protection
Control input signal : 4 – 20 mA, 0 – 20 mA, 0 – 10 V, 2 – 10 V. One or two digital inputs.
Position feedback : 0 – 20 mA, 4 – 20 mA (ICM)
3 Digital ON / OFF feedback•Resolution: 20 micron / step (0.02 mm stroke pr. step)
Total steps: 250 – 3650 depending on size•Auto Calibration, Neutral zone
In the event of a power failure, multiple fail-safe options are possible. During power failure, ICM can be selected to: Close ICM, Open ICM, Stay in the same position, as when power failure occurs. Go to a specific ICM valve opening degree
Hermetic magnetic motor
Enclosure: IP67 ~ NEMA 6
Approvals: CE, UL, CRN
Connectors for easy installation and servicing
Danfoss ICAD 600A / 1200A ensures accurate feedback on the valve position